Mixing Outdoor Air & Return Air

HVAC systems often mix outdoor air (OA) and return air (RA) before conditioning. The mixed air state determines coil loads, dehumidification potential, and comfort outcomes.

Key idea: mix on a dry-air basis

Psychrometric “mixing” is a mass balance problem. For best accuracy, mix properties using the dry-air mass flow as the weighting basis (and assume both streams are at roughly the same pressure).

The two values to mix

  • Humidity ratio (W): absolute moisture content (kg/kg_da).
  • Enthalpy (h): useful energy variable for HVAC loads (kJ/kg_da).

Mixing formulas (mass-weighted)

Let α be the outdoor air fraction on a dry-air basis (0–1). Then:

Wmix = α · WOA + (1 − α) · WRA
hmix = α · hOA + (1 − α) · hRA

After you have Wmix and hmix, you can compute the rest of the mixed air properties (Tdb, RH, Tdp, Twb, …) from that state.

What it looks like on a psychrometric chart

The mixed air point lies on the straight line between the OA and RA points on the chart. Its location along the line depends on the mixing fraction α.

Using FluidTool (practical workflow)

  1. Compute WOA and hOA from your outdoor air measurements (e.g., Tdb + RH).
  2. Compute WRA and hRA from your return air measurements.
  3. Choose a mixing fraction α (outdoor air fraction on a dry-air basis) and compute Wmix/hmix using the formulas above.
  4. In the humid air tool, switch inputs to W + H, enter Wmix and hmix, and read the resulting mixed air Tdb/RH/dew point/wet-bulb.