R1234ze(E) pressure temperature chart (PT)

An R1234ze(E) pressure temperature chart (PT chart) is a saturation lookup for R1234ze(E): it relates temperature and saturation pressure when liquid and vapor coexist in equilibrium. This is useful for thermodynamic interpretation, but it is not a universal “normal running pressure” diagnostic chart.

Pressure basis: absolute vs gauge

The table below is absolute pressure (kPa(a), bar(a), psi(a)). Many gauges display gauge pressure (relative to ambient). Converting requires local atmospheric pressure:

Pabs = Pgauge + Patm

Learn more: Gauge vs absolute pressure (psig vs psia).

Safety note

Refrigerants have safety classifications (toxicity/flammability) and their use is governed by codes and local regulations. This page is educational and provides property reference data only — always follow OEM procedures and applicable safety requirements.

R1234ze(E) saturation pressure vs temperature (reference table)

Generated using CoolProp (the same property engine used by FluidTool) at Q=0 saturation. Values are rounded for readability.

T (°C)T (°F)Psat (kPa(a))Psat (bar(a))Psat (psi(a))
-20-496.90.96914.1
-1014147.41.47421.4
032216.62.16631.4
1050308.43.08444.7
2068427.34.27362.0
3086578.35.78383.9
40104766.57.665111.2
50122997.29.972144.6
601401276.612.766185.2
701581611.016.110233.7

How to verify any row in FluidTool

  1. Open FluidTool with R1234ze(E) selected: /?fluid=R1234ze(E)
  2. Choose a Two-phase input pair (Temperature & Quality / T + Q).
  3. Set Q=0 and enter the temperature from the table to read Psat.