R1336mzz(E) pressure temperature chart (PT)

An R1336mzz(E) pressure temperature chart (PT chart) is a saturation lookup for R1336mzz(E): it relates temperature and saturation pressure when liquid and vapor coexist in equilibrium. This is useful for thermodynamic interpretation, but it is not a universal “normal running pressure” diagnostic chart.

Pressure basis: absolute vs gauge

The table below is absolute pressure (kPa(a), bar(a), psi(a)). Many gauges display gauge pressure (relative to ambient). Converting requires local atmospheric pressure:

Pabs = Pgauge + Patm

Learn more: Gauge vs absolute pressure (psig vs psia).

Safety note

Refrigerants have safety classifications (toxicity/flammability) and their use is governed by codes and local regulations. This page is educational and provides property reference data only — always follow OEM procedures and applicable safety requirements.

R1336mzz(E) saturation pressure vs temperature (reference table)

Generated using CoolProp (the same property engine used by FluidTool) at Q=0 saturation. Values are rounded for readability.

T (°C)T (°F)Psat (kPa(a))Psat (bar(a))Psat (psi(a))
-20-428.00.2804.1
-101446.20.4626.7
03272.80.72810.6
1050110.41.10416.0
2068161.71.61723.4
3086229.82.29833.3
40104318.13.18146.1
50122430.34.30362.4
60140570.25.70282.7
70158742.17.421107.6

How to verify any row in FluidTool

  1. Open FluidTool with R1336mzz(E) selected: /?fluid=R1336mzz(E)
  2. Choose a Two-phase input pair (Temperature & Quality / T + Q).
  3. Set Q=0 and enter the temperature from the table to read Psat.