R152A pressure temperature chart (PT)

An R152A pressure temperature chart (PT chart) is a saturation lookup for R152A: it relates temperature and saturation pressure when liquid and vapor coexist in equilibrium. This is useful for thermodynamic interpretation, but it is not a universal “normal running pressure” diagnostic chart.

Pressure basis: absolute vs gauge

The table below is absolute pressure (kPa(a), bar(a), psi(a)). Many gauges display gauge pressure (relative to ambient). Converting requires local atmospheric pressure:

Pabs = Pgauge + Patm

Learn more: Gauge vs absolute pressure (psig vs psia).

Safety note

Refrigerants have safety classifications (toxicity/flammability) and their use is governed by codes and local regulations. This page is educational and provides property reference data only — always follow OEM procedures and applicable safety requirements.

R152A saturation pressure vs temperature (reference table)

Generated using CoolProp (the same property engine used by FluidTool) at Q=0 saturation. Values are rounded for readability.

T (°C)T (°F)Psat (kPa(a))Psat (bar(a))Psat (psi(a))
-20-4120.71.20717.5
-1014181.51.81526.3
032264.02.64038.3
1050372.83.72854.1
2068512.95.12974.4
3086689.86.898100.0
40104909.39.093131.9
501221177.411.774170.8
601401500.715.007217.7
701581886.418.864273.6

How to verify any row in FluidTool

  1. Open FluidTool with R152A selected: /?fluid=R152A
  2. Choose a Two-phase input pair (Temperature & Quality / T + Q).
  3. Set Q=0 and enter the temperature from the table to read Psat.

Related